Arrived on site customer has flood has not tried it too much. 120v to transformer 27 out to the board. The board is failing to send this low voltage out on the thermostat wires and led is failing to light up. The fuse is in tact checked continuity. Board has failed from the floods and needs to be replaced. 2002 Goodman System has water up above the blower motor more than likely it will need replaced going to order both and bring both out to save a trip if we need the blower motor.

Near Seigman Ave, Whitehall, OH 43213
Whitehall, OH - Arrived on site customer has flood has not tried it too much. 120v to transformer 27 out to the board. The board is failing to send this low voltage out on the thermostat wires and led is failing to light up. The fuse is in tact checked continuity. Board has failed from the floods and needs to be replaced. 2002 Goodman System has water up above the blower motor more than likely it will need replaced going to order both and bring both out to save a trip if we need the blower motor.
Haidar H.

Haidar H.

Flame sensor reading found low again on a Goodman furnace. Advised to replace the sensor as it was cleaned prior and still having heating issues.

Near Whitehall, OH 43213
Whitehall, OH - Flame sensor reading found low again on a Goodman furnace. Advised to replace the sensor as it was cleaned prior and still having heating issues.
Chris M.

Chris M.

Lennox furnace pilot relight.

Near Shell Ct S, Whitehall, OH 43213
Whitehall, OH - Lennox furnace pilot relight.